Mysterious electrical anomalies, characterised by tiny frequency drops every 60 seconds, have been observed simultaneously on power grids across countries and continents for years. Dirk Witthaut, a researcher at Forschungszentrum Jülich in Germany, investigated the phenomenon after it was brought to his attention by Tennet Germany, the country's largest transmission system operator.
After years of investigative and modelling work, Witthaut and his team determined the cause. They discovered that many stationary batteries, ranging from data centre uninterruptible power supplies (UPSes) to large grid-scale batteries, check their state-of-charge every minute. As these devices are internet-connected, their internal clocks are nearly perfectly synchronised. While an individual check is imperceptible, the collective action creates a noticeable disturbance on the grid.
Evidence for this was found in Ireland, where data centres, each served by a fleet of UPSes, consumed 18% of the country's electricity load by 2022. Between 2016 and 2021, the minute-by-minute frequency drop on the Irish grid quadrupled from 3 milli-Hertz (mHz) to 12 mHz, with some recent drops exceeding 20 mHz.
Although Ireland's 50 Hz grid is designed to withstand swings of plus or minus 200 mHz, these drops can be troubling. If other loads also cause frequency sags, the additional disturbance from synchronised UPS checks could potentially push the grid towards blackout conditions or damage power plant equipment, particularly hydropower turbines.
The researchers suggest that adding some randomisation to the state-of-charge check schedule for UPS and grid-scale battery manufacturers could prevent the problem. They also noted that other internet of things (IoT) devices, such as smart ovens and Raspberry Pi clusters, can cause periodic power fluctuations, and many of these devices often remain unpatched.